HOPU Vertical Type Single Stage Vacuum Transformer Oil Purifier is popular in electric power industries, the machine is designed to purify and recover old insulating oil, like the transformer oil, mutual inductor oil, cable oil, and switch oils. The process increase the o.
Introduction:
Transformer oil maintenance is the key to transformer reliability, performance and longevity. Your transformer's insulating oil should be free from moisture, dissolved gases and particles that accumulate as the oil ages. Even some new oils may require treatment to limit these contents to acceptable levels.
HOPU Vertical Type Single Stage Vacuum Transformer Oil Purifier is popular in electric power industries, the machine is designed to purify and recover old insulating oil, like the transformer oil, mutual inductor oil, cable oil, and switch oils.
Features:
1) Adopts the automatic double floating ball liquid level control system, automatic constant temperature control system, automatic foam elimination control system, automatic pressure protection system, automatic interlock protection system to ensure the equipment and operator's safety.
2) With compact structure, easy operation and online oil purification. It can work with nobody supervision and be used under any environment.
3) It can be used together with regeneration device to discolor, remove acid, free carbon and lower the dielectric loss.
4) Triple filtration system with high filtration precision, holds much of sludge, remove the fine particulates out from the oil.
5) Unique degassing, dehydration material, its evaporation area one hundred times larger than conventional materials.
6) Adopts vertical type vacuum separation tank in which the atomized oil will have a longer retention time, then the efficiency of dehydration and degassification is higher.
7) The machine has the characteristics of small dimension and high efficiency, convenient movement, particularly suitable for live working in site.
Technical Parameter
Parameters | Unit | ZY-10 | ZY-20 | ZY-30 | ZY-50 | ZY-70 | ZY-150 | ZY-200 | ZY-300 | |
Flow rate | L/h | 600 | 1200 | 1800 | 3000 | 4200 | 9000 | 12000 | 60000 | |
Working vacuum | MPa | -0.06 ~ -0.095 | ||||||||
Working pressure | MPa | 0.4 | 0.4 | ≤0.4 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | |
Breakdown voltage | KV | ≥55 | ≥55 | ≥55 | ≥60 | ≥60 | ≥60 | ≥60 | ≥65 | |
Moisture | PPM | ≤5 | ||||||||
Gas content | % | ≤0.1 | ||||||||
Impurity content | μ | ≤5 | ||||||||
Temperature range | ℃ | 10 ~ 80 | ||||||||
Power supply | 50HZ380V(or as needed) | |||||||||
Working noise | dB(A) | 61 | 63 | 70 | 70 | 75 | 70 | 70 | 70 | |
Heating power | KW | 11 | 13 | 15 | 30 | 48 | 52.5 | 57.5 | 60 | |
Total power | KW | 12.5 | 14.5 | 16.5 | 33.5 | 51.5 | 57.5 | 65.5 | 68 | |
Inlet/outlet caliber | mm | φ25 | φ25 | φ25 | φ32 | φ40 | φ50 | φ50 | φ60 | |
Weight | Kg | 150 | 200 | 260 | 300 | 400 | 450 | 550 | 600 | |
Size | L | mm | 1050 | 1050 | 1100 | 1200 | 1450 | 1600 | 1800 | 1900 |
W | mm | 750 | 750 | 800 | 950 | 950 | 1100 | 1200 | 1200 | |
H | mm | 1350 | 1350 | 1400 | 1500 | 1650 | 1800 | 1900 | 1900 |
Optional:
A : Without Enclosure, open and Stationary type
B : With Enclosure, Cubicle and Stationary type
C : With Skid base type
D : Mounted on casters
E : Mounted on Single-axle Trailers (Pneumatic tyre, Speed selectable)
F : Mounted on Double-axle Trailers (Pneumatic tyre, Speed selectable)
You May also be interested in:
A: Transformer Oil Tester, Testing the insulating oil's dielectric strenght
B: Vacuum Pumping Set, pumping the transformer
C: Moisture Meter, measuring the water content in the transformer oil
D: Flow meter, measuring the flow oil quanity through the machine
We are profession exporter, provide service worlwide!
Your inquiry will be replied within 12 hours due to time zone difference
Your inquiry is warmly welcomed!
HOPU Website: www.hopufiltration.com
Branch 1: www.hpoilsolution.com